Fire, Smoke and Insulated Curtains

Fire, Smoke & Insulated Curtains.

The Fire-Gard curtain provides the benefits of an off-the-shelf lightweight design which eliminates the problems of steel shutters. It requires less preparation time and no special steelwork structure to install.

Designed for openings of up to 32m wide x 8m high in the fire compartment wall, the Fire-Gard curtain is a totally new concept. It eliminates the dangers posed by heavy steel shutters which could drop causing casualties or breakages. It is especially suited to clean, hygienic environments such as kitchens to hospitals, or as equally at home over windows and reception areas.

The Fire-Gard curtain is tested to BS 476 part 22 & 4 hour fire shutter performance to BS 7346 part 3 for smoke.

Smoke-and-Fire-curtain-500x400
Smoke-and-fire-curtains-500-image-2

Specifications

The Fire Curtains are manufactured from woven glass fibre reinforced with stainless steel wire and coated both sides with a micronized aluminium polymer which will automatically descend under the power of gravity upon receipt of a signal from the fire-alarm panel and automatically retract when the signal is removed. The lower edge of the curtains will incorporate a twin inverted, Galvanised steel angle which acts as a weight bar to anable the curtain to unwind upon receipt of a signal from the fire alarm panel, this helps to stabilise the curtains and provides a stop against the underside of the head box.
Technical Specifications
CurtainsHarlech Industrial Doors has specially developed the 240+ Fabric. This complies fully with the most demanding requirements for specifiers and Fire Safety Authorities in countries where legislation exists for Smoke and Fire control systems.
240+ Fabric exceeds the performance required for materials used in the manufacture of smoke and fire curtains and blinds, smoke screens; cavity walls and roof void fire barriers etc.
240+ Fabric is a woven glass fibre fabric, reinforced with stainless steel wire and coated on both sides with a specially formulated micronized aluminium polymer which provides an effective heat reflective surface as well as other properties required for materials used in the manufacture of smoke and fire curtains and blinds, smoke screens, cavity wall and roof void fire barrier applications, when installed in public buildings with open areas, where public safety is paramount, both onshore and offshore.
As a coated fabric, 240+ Fabric offers advantages over similarly approved materials, in terms of minimal smoke permeability and reduced skin irritation. The material is flexible and easy to piece together to install.
Bottom RailA strong roll formed bottom rail 1.6mm thick fitted to bottom of the curtain.
RollerThe roller size depends on the size motors used, which are 24 volt DC with gravity, fail safe system up to certain sizes. The head box dimensions start at 150mm x 150mm up to 300mm x 300mm depending on the dimensions of the curtain, Galvanised mild steel head box which is normally bolted to the fabric of the building. Galvanised steel side guides complete with our fabric retaining mechanism will be supplied to form a seal between the curtain fabric and the structure of the building. The channel guides very from 50mm to 150mm with an overall sizeof between 75mm to 200mm per side depending on the width of the opening.
GuidesGalvanised steel side guides complete with our fabric retaining mechanism will be supplied to form a seal between the curtain fabric and the structure of the building. The channel guides very from 50mm to 150mm with an overall size of between 75mm to 200mm per side depending on the width of the opening.
Operation24 Volt DC motor with audio visual panel, 96 hour battery backup, Delay before closure and two stage closing, Auto and manual reset & volt free alarm connection
FinishGalvanised as standard or Powder coated (any colour from our standard range) as an extra charge.
Fire Rating60 min | 120 min| 240 min
Radiation Intensity20 min – 1.21KW/m2, 30 min – 1.73KW/m2, 60 min – 5.32KW/m2, 90 min – 7.23 KW/m2, 120 min – 10.89 KW/m2
Size MaximumUnlimited Width x 6000mm Height (All as report 173621)
PerformanceCE marked 01 May 2005: Product Standard BS EN 13241 – 1 (2003)
BSEN 12604 (2000) Mechanical aspects – Requirements
BS EN 12453 (2001) Safety in use of power operated doors – Requirements
BS EN 12424 (2000) Resistance to wind load : Class 5
BS EN 12206 – 1 (2004) Application of architectural powder coating
ApprovalsAll Fire Doors Are Constructed in accordance with BS EN 1634-1 : 2000 and British Standards 476. Part 22: 1987 and British Standards 476 Part 31.1
Optional ExtrasThe curtain, guides, fixing angles, end plates and hood, to be powder coated any colour from our standard RAL range.
If the curtain is the only means of exit from the building we would strongly recommend that a push button control is installed on the inside to prevent trapping.